Difference between revisions of "Data Center Specifications"
Line 1: | Line 1: | ||
+ | == '''Facility''' == | ||
+ | |||
'''Facility Size''' | '''Facility Size''' | ||
*Main floor: 5,000 square feet | *Main floor: 5,000 square feet | ||
Line 21: | Line 23: | ||
*On-site, staffed 24 hours a day, 7 days per week, 365 days per year. Alarm system enabled with cameras and DVR recorders on all points of ingress/egress and numerous internal spaces of the building. Dual Biometric authentication security system installed. Tri-Token authorization system. | *On-site, staffed 24 hours a day, 7 days per week, 365 days per year. Alarm system enabled with cameras and DVR recorders on all points of ingress/egress and numerous internal spaces of the building. Dual Biometric authentication security system installed. Tri-Token authorization system. | ||
− | '''Telecommunications''' | + | == '''Telecommunications''' == |
*XO Communications - 10Gb | *XO Communications - 10Gb | ||
*NLayer - 10Gb | *NLayer - 10Gb | ||
Line 34: | Line 36: | ||
*Comcast | *Comcast | ||
--> | --> | ||
+ | |||
+ | == '''Power & Cooling''' == | ||
'''Commercial Power''' | '''Commercial Power''' | ||
Line 67: | Line 71: | ||
− | '''Bandwidth''' | + | == '''Bandwidth''' == |
XMission uses the industry standard 95th Percentile model to bill for bandwidth. This allows you to only pay for the bandwidth you use while offering the benefits of faster speed and greater throughput. | XMission uses the industry standard 95th Percentile model to bill for bandwidth. This allows you to only pay for the bandwidth you use while offering the benefits of faster speed and greater throughput. |
Revision as of 14:39, 9 August 2012
Facility
Facility Size
- Main floor: 5,000 square feet
- Second floor: 5,000 square feet
Completed
- 2nd quarter 2001
Raised Floor Area
- 3,000 Usable Square Feet (USF) for colocation
Raised Floor System
- 12" concrete core raised floor manufactured by Maxcess/Tate
Floor Load
- 250 pounds per square foot on slab
Building Access
- 24 hours a day, 7 days per week, 365 days per year
Building Security
- On-site, staffed 24 hours a day, 7 days per week, 365 days per year. Alarm system enabled with cameras and DVR recorders on all points of ingress/egress and numerous internal spaces of the building. Dual Biometric authentication security system installed. Tri-Token authorization system.
Telecommunications
- XO Communications - 10Gb
- NLayer - 10Gb
- Level3 - 10Gb
- Cogent
Power & Cooling
Commercial Power
- Independent underground 12,000 V feed from a new Rocky Mountain Power substation. Dedicated connection with no other building load. buried under mass-transit system to reduce construction risk.
- Building load handled by 2,500 KVA (2 Megawatt) Transformer over sized for extra protection and durability. Transformer is secured externally from building.
Generator
- Two 500 KW Cummins DFED Gensets with a 18.8 Liter turbo diesel/Aftercooled KTA-19 engine. Two currently handling facility load with the third to be wired as a standby genset for N+1 redundancy.
- Low fuel consumption and rigorous testing schedule allows long term power generation for facilities needs.
Power Infrastructure
- Cummins Power Generation OTPC transfer switch gear rated for 1200 Amps at 480 Volts. Detects faults in power feeds, turns on emergency power generators, verifies power condition and if all is ok, transfers facility load to the emergency power equipment.
- Cummins Power Generation BTPC series bypass isolation transfer switch gear rated for 1200 Amps at 480 Volts. The BTPC series allows power to be routed around a failed transfer switch unit.
- Three Mitsubishi 9800 AD UPS's (Uninterruptible Power Supply) 225 KVA (190 KW). Using Mitsubishi IGBT technology power effeciency improves with cleaner total power to the client gear.
- Seven (7) 480 Volt/3 Phase Power Distribution Units/Transformers
- Two (2) 208 Volt 3Phase Remote Distribution Units
- Active monitoring of power loads and infrastructure utilization allow accurate planing of load redundancy at the client level.
Fuel Tank
- Single 366 Gal double-lined fuel tanks
- 25 gallon day tank
HVAC
- Liebert Deluxe System 3 CRAC (Computer Room Air Conditioner) units connected to over-sized GlyCool cooling towers via redundant dual pump system. N+1 configuration allows full proper service work without change in temperature.
- Five (5) cooling towers, 30-45 ton cooling capacity each
- Three (3) 30-ton CRAC units
- Two (2) 20-ton CRAC units
- One (1) 10-ton CRAC unit
- Two (2) 5-ton CRAC units
- Designed to N+1 redundancy
- 2 foot return air Hot Plenum in ceiling. Utilizing new thermal technologies, a fully functional hot plenum is used to overclock CRAC units, and provide better heat removal efficiency.
- 10 Feet vertical workable space above raised floor.
Bandwidth
XMission uses the industry standard 95th Percentile model to bill for bandwidth. This allows you to only pay for the bandwidth you use while offering the benefits of faster speed and greater throughput.
To determine your billable utilization, otherwise known as your “95th percentile rate,” XMission measures your bandwidth usage at regular intervals over a 30.5 day period. At the end of the period, XMission will discard the top 5% of your inbound and outbound bandwidth samples separately (approximately 36 hours worth of traffic). The remaining measurement becomes your 95th percentile rate.
If your 95th Percentile Rate exceeds your Committed Data Rate (CDR), XMission will post-bill you for any overages at the CDR price per Megabit.
More details about 95% billing can be found here: http://en.wikipedia.org/wiki/Burstable_billing